Kablo Yapısı
CONDUCTOR: Electrolytic annealed, class 5 stranded tinned copper wires
SEPERATOR: A suitable tape may be applied over the conductor
INSULATION: EI4 type cross-linked elastomeric compound, EPR (EN 50363-1)
SHEATH: EM7 type cross-linked elastomeric compound (EN 50363-2-1)
COLOR: Black
Çalışma Karakteristlikleri
RATED VOLTAGE: 600/1000 V (U0/U)
AC TEST VOLTAGE: 4 kV
OPERATING TEMPETATURE: -40°C to +90°C
CONDUCTOR SHORT-CIRCUIT TEMP.: 250°C (Max. 5 sec.)
MIN. INSTALLATION TEMP.: -25°C
MIN. BENDING RADIUS: Based on EN 50565-1 Tab. 3
CURRENT CARRYING CAPACITIES: VDE 0298-4 Tab.13 , IEC 60364-5-52 Tab. B.52.12 & Tab. C.52.1
Teknik Özellikleri
| Cross Section (mm²) | Nominal Overall Diameter (mm) | Approximate Weight (kg / km) |
Min.Bending Radius (free movement) (mm) |
Max. Resistance of Conductors at 20°C (ohm / km) |
|---|---|---|---|---|
| 1×10 | 11,50 | 215 | 1,95 | 35 |
| 1×16 | 13,00 | 296 | 1,24 | 52 |
| 1×25 | 15,60 | 429 | 0,795 | 62 |
| 1×35 | 16,50 | 531 | 0,565 | 66 |
| 1×50 | 17,80 | 674 | 0,393 | 71 |
| 1×70 | 19,70 | 880 | 0,277 | 79 |
| 1×95 | 22,10 | 1130 | 0,21 | 88 |