Kablo Yapısı
CONDUCTOR : Electrolytic annealed, class 5 stranded plain copper wires (tinned conductor on request)
SEPERATOR : A suitable tape may be applied over the conductor
INSULATION : EI4 type rubber (EPR) compound
CORE IDENTIFICATION: Acc. to HD 308
INNER SHEATH: EM2 or EM3 type elastomeric rubber compound (if outer sheath thickness is greater than 2.4 mm)
OUTER SHEATH : EM2 type elastomeric rubber compound
COLOR: Black (other colors on request)
Çalışma Karakteristlikleri
CONSTRUCTION : EN 50525-2-21, DIN VDE 0282-4, BS 6500 BS 7919, IEC 60245-4
GENERAL REQUIREMENTS : EN 50525-1, HD 22.1, DN VDE 0282-1, IEC 60245-1
GUIDE TO USE : HD 516, DIN VDE 0298-300
ELECTRICAL TESTS : EN 50395, IEC 60245-2
NON – ELECTRICAL TESTS : EN 50396, IEC 60245-2
CONDUCTOR RESISTANCE : EN / IEC 60228, HD 383, DIN VDE 0295, BS 6360
WORKING TEMPERATURE IN MOBILE USE : -25ºC / +60ºC
IN FIXED USE : -35ºC / +85ºC
CONDUCTOR SHORT – CIRCUIT TEMP. : Max. 200ºC
TEMP. ON CABLE SURFACE : Max. +50ºC
MIN. INSTALLATION TEMP. : -25ºC
MIN. BENDING RADİUS : EN 50565-1 Table 3
MAX. TENSILE LOAD : 15 N / mm2
CURRENT CARRYING CAPACITIES : IEC 60 364-5-52, VDE 0298-4, EN 50565-1
FLAME RETARDANT : IEC 60332-1-2, DIN VDE 0482-332-1-2
OIL RESISTANT : EN 50363-2-1, IEC 60811-404
Teknik Özellikleri
| Construction | Cross Section |
Nominal Overall Diameter (mm) |
Approximate Weight (kg / km) |
Max Resistance of Conductors at 20°C (ohm / km) |
Current Carrying Capacity for fixed usage (A) |
|---|---|---|---|---|---|
| BCL5 / EI4 / EM2 | 1×2,5 mm² | 6,4 | 65 | 7,98 | 26 |
| BCL5 / EI4 / EM2 | 1×4 mm² | 7,3 | 90 | 4,95 | 34 |
| BCL5 / EI4 / EM2 | 1×6 mm² | 8,1 | 115 | 3,30 | 43 |
| BCL5 / EI4 / EM2 | 2×2,5 mm² | 10,6 | 165 | 7,98 | 26 |
| BCL5 / EI4 / EM2 | 2×4 mm² | 12,2 | 230 | 4,95 | 43 |
| BCL5 / EI4 / EM2 | 2×6 mm² | 13,6 | 300 | 3,30 | 60 |